SASUN INTERNATIONAL ELECTRIC CO., LTD.
|
Price: | 1500.0 USD |
Payment Terms: | T/T,L/C |
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Place of Origin: | Zhejiang, China (Mainland) | Brand Name: | SASUN | Model Number: | KYN28-12 switchgear |
12KV swichgear: | metal-clad enclosed switchgear | rated current: | 630~2000A | rated current of dynamic stability (4S): | 16/20/25/31.5/40/50KA |
Protection degree.: | IP2X&IP4X |
Packaging Details: | Packaging Detail: wooden box |
Delivery Detail: | 35days after getting prepayment |
KYN28A-12(Z) Metalclad AC Indoor Enclosed Switchgear,
Withdrawable type, 3KV,6KV,11KV , 12KV
1. General Description
1.1 Application: In the power system of 3.6 to 12kV, for control, protection and monitoring.VCBs produced
By CNHK or VCBs produced by other manufactures could be installed in the switchgear panel.
1.2 Standards : IEC 62271-200
1.3 Parameters: Rated voltage: 3.6V
1.4 Rated current: 630-5000A
1.5 Rated short-circuit breaking current: 16kA
2.Features:
2.1.Compact design
2.2.Easy operation and installation
2.3.Reliable interlock
2.4.Less Maintenance
3.Technical Data
No. | Item | Unit | Data | |
3.1 | Rated voltage | kV | 3.6,7.2,12 | |
3.2 | Rated current of circuit breaker | A | 630,1250,1600,2000,2500,3150,4000,5000 | |
Rated current of switchgear | A | 630,1250,1600,2000,2500,3150,4000,5000 | ||
3.3 | Rated frequency | Hz | 50 | |
3.4
| Rated short-circuit breaking current | kA | 16,20,25,31.5,40,50 | |
Rated short-time withstand current | kA | 16,20,25,31.5,40,50 | ||
Rated short circuit continuous time | s | 4 | ||
3.5 | Rated peak withstand current | kA | 40,50,63,80,100,125 | |
Rated short-circuit closing current(peak) | kA | 40,50,63,80,100,125 | ||
3.6 | Rated insulation level: 1min power frequency withstand voltage | kV | 24,32,42 between poles, pole to earth | |
kV | 24,32,48 between open contacts | |||
3.7 | Rated insulation level: Lighting impulse withstand voltage(peak) | kV | 40,60,75 between poles, pole to earth | |
kV | 46,70,85 between open contacts | |||
3.8 | Rated power frequency withstand voltage | kV | 95/1min | |
3.9 | Protection level | Switchgear shell | IP3X | |
Compartments(door opened) | IP2X when the CPT and CB doors are open. |
Note: 1.The short circuit capacity of the current transformer should be separately considered.
2. See technical parameters of ZN63A(VS1)-12 in related product of our company.